function [DTR,AEQ,PUL_loading]=Finding_DTR_with_RHC(PUL,AMB,TIM,r_limit,PUL_loading)
%% Purpose
% This function applies receding horizong control to determine DTR of transformer
% Input:
% PUL - actual load at t- and forecast load at t+, pu
% AMB - actual ambient temperature at t- and forecast amb.temperature at
% TIM - time (minutes) vector
% r_limit - a right limit in minutes for corresponding hour
% PUL_loading - a historical transformer loading
% Output:
% DTR - Dynamic Thermal Rating of transformer, pu
% AEQ - Aging equivalent, pu
% PUL_loading - transformer loading,pu
% Contacts:
% Linkedin - https://www.linkedin.com/in/ildar-daminov/
% Researchgate - https://www.researchgate.net/profile/Ildar-Daminov-2
% GitHub - https://github.com/Ildar-Daminov
%% Function execution
% Depending on initial HST and AEQ, different algoritms may be applied.
% 1. if max(HST(r_limit+1:end))<=140|| AEQ<=1 then we apply algorithm 1
% 2. if max(HST(r_limit+1:end))>140|| AEQ>1 then we apply algorithm 2
% Note that there is a specific case for 2 situation then algorithm 3
% Algorithm 1: set DTR at remaining horizon equal to reference DTR (similar
% to reference DTR)) but considering the remaining insulation resource at
% t+
% Algortihm 2: set the DTR at off peak periods equal to 1 (nominal rating)
% and reduced transformer loading at peak periods until the condition
% "max(HST(r_limit+1:end))<=140|| AEQ<=1" is not met
% Algortihm 3 (special case):
% set loading at interval t+
PUL_loading(r_limit+1:end,1)=PUL(r_limit+1:end,1);
% loading at t- and forecast at t+ (without limitation by DTR)
PUL=PUL_loading;
% estimate thermale regime with consideration of t- and t+
[HST,~,AEQ,Current_ageing,~,~,~]=IEEE_thermal_model(AMB,PUL,TIM);
% find residual insulation resource
residual_ageing=1440-Current_ageing(r_limit);
if max(HST(r_limit+1:end))>140|| AEQ>1 % then we apply algorithm 2
% Set a static limit ==1 pu
static_limit=linspace(1,1,length(PUL))';
% Find the indexes where load is below of nominal rating
off_peak_interval=find(PUL<static_limit);
% Find in this array the indexes more than r limit
index_r_limit=off_peak_interval>r_limit;
% Adjust off peak interval according to r limit
off_peak_interval=off_peak_interval(index_r_limit);
% Set the DTR to nominal rating for this off peak interval
PUL(off_peak_interval)=1;
% Find DTR at time interval t+
[DTR,~]=algorithm_2(PUL,AMB,TIM,r_limit);
elseif max(HST(r_limit+1:end))<=140|| AEQ<=1 % then we apply algorithm 1
% Estimate reference_DTR area at interval t+
[reference_DTR]=algorithm_1(AMB,r_limit,residual_ageing,PUL);
% Checking if a load is always below DTR
index=reference_DTR(r_limit+1,1)>PUL(r_limit+1,1);
if all(index==1) % if load is always below DTR
% Determine DTR as reference_DTR
DTR=reference_DTR;
else % if PUL is higher than reference_DTR even once
% Then we apply algorithm 3 which maximizes the square under load profile
% if we have the residual resource. In this case DTR is determined
% by algorithm 3
[DTR,AEQ]=algorithm_3(PUL,AMB,TIM,r_limit,residual_ageing);
disp('ATTENTION: algorithm_3 is given for information purpoes. See NB in code')
% NB: algorithm 3 represents a possible heuristic logic of setting
% DTR. However, the logic is not neccesary the optimal one because
% it was not the goal of the paper. Therefore, the reader should
% consider algorithm 3 as one of many possible logics for special case.
end % end of "if all(index==1)"
end % end of if max(HST(r_limit+1:end))>140|| AEQ>1
end % end of function