Variable CHW Flow Chillers Operate unexpectedly #10965
Labels
Triage
Issue needs to be assessed and labeled, further information on reported might be needed
UnconfirmedDefect
Defect has not yet confirmed to be an actual issue
Issue overview
The bug is reported in detail on UnmetHours. Below is an extract from UnmetHours.
The bug occurs when the following conditions are met. The last condition is particularly important.
Chiller:Electric:EIR
.Pump:VariableSpeed
, andChiller Flow Mode
ofChiller:Electric:EIR
is set toLeavingSetpointModulated
.Design Minimum FLow Rate
ofPump:Variable:Speed
is not 0.Load Distribution Scheme
ofPlant Loop
isSequentialUniformPLR
,SequentialLoad
orOptimal
.Leaving Chilled Water Lower Temperature Limit
ofChiller:Electric:EIR
is the same as (or closer to) the leaving chilled water temperature setpoint specified by a setpoint manager e.g.SetpointManager:Scheduled
.When the cooling load is small enough to be handled by one chiller, only the chiller should be ON and the remaining chillers should be OFF because the load distribution is set to be sequential, but this is not the case under the above conditions. The cooling load is distributed uniformly to all or most of chillers as if
Load Distribution Scheme
isUniformLoad
orUniformPLR
. That's the bug.Operating System (Multiple choices)
Windows
Operating System Version
11
Version of EnergyPlus
24.2.0
Unmethours link or helpdesk ticket number
https://unmethours.com/question/101114/variable-chw-flow-chillers-operate-unexpectedly/
Defect file
Please find the defect file in the following link.
https://drive.google.com/drive/folders/1AxBgEGGMWMFcnhZhwLuEtCn1eCVr1HCw?usp=drive_link
The text was updated successfully, but these errors were encountered: