PlantLoop object order can lead to water-to-water heat pump (WWHP) being missed as a heat recovery unit #10968
Labels
Triage
Issue needs to be assessed and labeled, further information on reported might be needed
UnconfirmedDefect
Defect has not yet confirmed to be an actual issue
Milestone
Issue overview
WWHP heat recovery units should not add to the size of the plant (i.e., it is considered a pass-through component). There are times when the order of the PlantLoop objects can miss the fact that the WWHP is a heat recovery unit and increase the plant water flow rate unnecessarily.
The defect file, a file created from example file PlantLoopHeatPump_EIR_LargeOffice-2-AWHP-AuxBoiler-Pri-Sec-4PipeBeam, has a WWHP heat recovery unit and shows the plant loop flow rate as:
While the original example file has a plant loop flow rate of:
Defect file:
PlantLoopHeatPump_EIR_LargeOffice-2-AWHP-AuxBoiler-Pri-Sec-4PipeBeam-WWHP_HR.zip
Issue courtesy of Trane North America, Inc.