DocumentationRelated primarily on the LaTeX-based EnergyPlus documentationRelated primarily on the LaTeX-based EnergyPlus documentationTriageIssue needs to be assessed and labeled, further information on reported might be neededIssue needs to be assessed and labeled, further information on reported might be needed
Description
General Summary
It appears that the units in the left hand size of Equation 2.1 are incorrect.
Detailed Description
The zone volume needs to be added to the left had size of Equation 2.1 in order for the units to work out correctly. Cz is defined as the zone air density multiplied by the zone air specific heat and the sensible heat capacity multiplier. The units for zone air density are kg/m3, the units for zone air specific heat are J/kg•°C, and the sensible heat capacity multiplier is unitless. As written, the units for Cz resolve to J/°C•m3 when they should be J/°C. Adding the zone volume to the left had size of Equation 2.1 corrects this unit error.
Possible Implementation
Add the zone volume to the left had size of Equation 2.1.
Reactions are currently unavailable
Metadata
Metadata
Assignees
Labels
DocumentationRelated primarily on the LaTeX-based EnergyPlus documentationRelated primarily on the LaTeX-based EnergyPlus documentationTriageIssue needs to be assessed and labeled, further information on reported might be neededIssue needs to be assessed and labeled, further information on reported might be needed