Issue overview
Follow up to #9052.
Testing shows the report variables for parent energy are different. It appears that the packaged terminal model reports correctly since there can be a latent cooling rate during heating mode when outdoor air is considered. Suggest adopting the method used by PTHP.
PTHP:
Zone Packaged Terminal Heat Pump Total Cooling Rate
Zone Packaged Terminal Heat Pump Sensible Cooling Rate
Zone Packaged Terminal Heat Pump Latent Cooling Rate
Zone Packaged Terminal Heat Pump Total Heating Rate
Zone Packaged Terminal Heat Pump Sensible Heating Rate
Zone Packaged Terminal Heat Pump Latent Heating Rate
state.dataPTHP->PTUnit(PTUnitNum).TotCoolEnergyRate = std::abs(min(0.0, QTotUnitOut));
state.dataPTHP->PTUnit(PTUnitNum).TotHeatEnergyRate = std::abs(max(0.0, QTotUnitOut));
state.dataPTHP->PTUnit(PTUnitNum).SensCoolEnergyRate = std::abs(min(0.0, QSensUnitOutNoATM));
state.dataPTHP->PTUnit(PTUnitNum).SensHeatEnergyRate = std::abs(max(0.0, QSensUnitOutNoATM));
state.dataPTHP->PTUnit(PTUnitNum).LatCoolEnergyRate = std::abs(min(0.0, (QTotUnitOut - QSensUnitOutNoATM)));
state.dataPTHP->PTUnit(PTUnitNum).LatHeatEnergyRate = std::abs(max(0.0, (QTotUnitOut - QSensUnitOutNoATM)));
UnitarySystem:
Unitary System Total Cooling Rate
Unitary System Sensible Cooling Rate
Unitary System Latent Cooling Rate
Unitary System Total Heating Rate
Unitary System Sensible Heating Rate
Unitary System Latent Heating Rate
if (state.dataUnitarySystems->HeatingLoad) {
if (QTotUnitOut > 0.0) { // heating
this->m_TotCoolEnergyRate = 0.0;
this->m_SensCoolEnergyRate = 0.0;
this->m_LatCoolEnergyRate = 0.0;
this->m_TotHeatEnergyRate = QTotUnitOut;
this->m_SensHeatEnergyRate = std::abs(max(0.0, QSensUnitOut));
this->m_LatHeatEnergyRate = std::abs(max(0.0, (QTotUnitOut - QSensUnitOut)));
} else {
this->m_TotCoolEnergyRate = std::abs(QTotUnitOut);
this->m_SensCoolEnergyRate = std::abs(min(0.0, QSensUnitOut));
this->m_LatCoolEnergyRate = std::abs(min(0.0, (QTotUnitOut - QSensUnitOut)));
this->m_TotHeatEnergyRate = 0.0;
this->m_SensHeatEnergyRate = 0.0;
this->m_LatHeatEnergyRate = 0.0;
}
} else {
if (QTotUnitOut <= 0.0) { // cooling
this->m_TotCoolEnergyRate = std::abs(min(0.0, QTotUnitOut));
this->m_SensCoolEnergyRate = std::abs(min(0.0, QSensUnitOut));
this->m_LatCoolEnergyRate = std::abs(min(0.0, (QTotUnitOut - QSensUnitOut)));
this->m_TotHeatEnergyRate = 0.0;
this->m_SensHeatEnergyRate = 0.0;
this->m_LatHeatEnergyRate = 0.0;
} else {
this->m_TotCoolEnergyRate = 0.0;
this->m_SensCoolEnergyRate = 0.0;
this->m_LatCoolEnergyRate = 0.0;
this->m_TotHeatEnergyRate = QTotUnitOut;
this->m_SensHeatEnergyRate = std::abs(max(0.0, QSensUnitOut));
this->m_LatHeatEnergyRate = std::abs(max(0.0, (QTotUnitOut - QSensUnitOut)));
}
}
The major difference is in the latent cooling or heating energy since total and sensible cooling or heating occur when the unit is in cooling or heating mode, respectively. Figure compares example file PackagedTerminalHeatPump from V9.5 to V9.6.
Details
Some additional details for this issue (if relevant):
- Platform (Operating system, version)
- Version of EnergyPlus (if using an intermediate build, include SHA)
- Unmethours link or helpdesk ticket number
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
- Defect file added (list location of defect file here)
- Ticket added to Pivotal for defect (development team task)
- Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
Reactions are currently unavailable