Opening /dev/ttyUSB0 at 9600 bauds (E, 8, 1)
[02][03][00][8C][00][0A][04][15]
Waiting for a confirmation...
<02><03><14><24><9E><42><A6><00><00><00><00><00><00><00><00><36><ED><43><79><00><00><00><00><04><73>
[02] - The Slave Address (02 hex = address 2 )
[03] - The Function Code 3 (read Analog Output Holding Registers)
[00][8C] - The Data Address of the first register requested.
( 008C hex = 140 , + 40001 offset = input #40141 )
[00][0A] - The total number of registers requested. (read 10 registers 40141 to 40151)
[04][15] - CRC
<02> - The Slave Address (02 hex = address 2 )
<03> - The Function Code 3 (read Analog Output Holding Registers)
<14> - The number of data bytes to follow (10 registers x 2 bytes each = 20 bytes)~14HEX
<24><9E>- The contents of register 40141 - 36 158
<42><A6>- The contents of register 40142 - 66 166
<00><00>- The contents of register 40143 -
<00><00>- The contents of register 40144 -
<00><00>- The contents of register 40145 -
<00><00>- The contents of register 40146 -
<36><ED>- The contents of register 40147 - 54 237
<43><79>- The contents of register 40148 - 67 121
<00><00>- The contents of register 40149 -
<00><00>- The contents of register 40150 -
<04><73>- CRC
Voltage 140
Voltage - Phase 1 142
Voltage - Phase 2 144
Voltage - Phase 3 146
Current 148
Current - Phase 1 150
Current - Phase 2 152
Current - Phase 3 154
Active Energy 158