Hydronic heating water systems (HWS) contain boilers (BLR) to heat the water and pumps (PMP) to distribute the heated water to downstream equipment and/or to circulate the water through the boilers.
- It must handle water for the purposes of heating.
This version of HWS has a single set of variable speed pumps which serve boilers and downstream equipment.
- The fields associated with individual devices (e.g., individual supply water temps for each boiler) get mapped to those individual devices while system level telemetry (e.g., system supply water temperature) gets assigned to the heating water system directly.
BLDG-1:
type: FACILITIES/BUILDING
ZONE-1:
connections:
BLDG-1: CONTAINS
VAV-1: FEEDS
type: FACILITIES/ZONE
ZONE-2:
connections:
BLDG-1: CONTAINS
FCU-1: FEEDS
type: FACILITIES/ZONE
# Define the system that all equipment is part of.
# It will feed all downstream equipment.
HWSYS-BLDG-1:
cloud_device_id: 1234
connections:
BLDG-1: CONTAINS
type: HVAC/HWS_...
translation:
supply_water_temperature_sensor:
present_value: points.sys_swt.present_value
units:
key: pointset.points.sys_swt.units
values:
degrees_fahrenheit: 'deg-F'
differential_pressure_sensor:
present_value: points.sys_dp.present_value
units:
key: pointset.points.sys_dp.units
values:
pascals: 'Pa'
...
# Define the equipment for the system and connect it to the system
# Additional intrasystem connections can be made as well.
BLR-1:
cloud_device_id: 12234
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: HAS_PART
PMP-1: FEEDS
PMP-2: FEEDS
PMP-3: FEEDS
type: HVAC/BLR_...
translation:
supply_water_temperature_sensor:
present_value: points.swt.present_value
units:
key: pointset.points.swt.units
values:
degrees_fahrenheit: 'deg-F'
...
BLR-2:
cloud_device_id: 12334
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: HAS_PART
PMP-1: FEEDS
PMP-2: FEEDS
PMP-3: FEEDS
type: HVAC/BLR_...
translation:
supply_water_temperature_sensor:
present_value: points.swt.present_value
units:
key: pointset.points.swt.units
values:
degrees_fahrenheit: 'deg-F'
...
BLR-3:
cloud_device_id: 12344
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: HAS_PART
PMP-1: FEEDS
PMP-2: FEEDS
PMP-3: FEEDS
type: HVAC/BLR_...
translation:
supply_water_temperature_sensor:
present_value: points.swt.present_value
units:
key: pointset.points.swt.units
values:
degrees_fahrenheit: 'deg-F'
...
PMP-1:
cloud_device_id: 12345
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: CONTAINS
type: HVAC/PMP_...
translation:
run_command:
present_value: points.cmd.present_value
states:
OFF: 'false'
ON: 'true'
...
PMP-2:
cloud_device_id: 123432
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: CONTAINS
type: HVAC/PMP_...
translation:
run_command:
present_value: points.cmd.present_value
states:
OFF: 'false'
ON: 'true'
...
PMP-3:
cloud_device_id: 123443
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: CONTAINS
type: HVAC/PMP_...
translation:
run_command:
present_value: points.cmd.present_value
states:
OFF: 'false'
ON: 'true'
...
# Define the equipment which is fed from the system, and connect it to the systems.
FCU-1:
cloud_device_id: 123453
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: FEEDS
type: HVAC/FCU_DFSS_DFVSC_...
translation:
heating_water_valve_percentage_command:
present_value: points.htg_valve_percentage_command.present_value
units:
key: pointset.points.htg_valve_percentage_command.units
values:
percent: '%'
...
VAV-1:
cloud_device_id: 12346526
connections:
BLDG-1: CONTAINS
HWSYS-BLDG-1: FEEDS
type: HVAC/VAV_SD_DSP_...
translation:
heating_water_valve_percentage_command:
present_value: points.hwv.present_value
units:
key: pointset.points.hwv.units
values:
percent: '%'
...