Modbus Extension (0x09)

This extension is from the hardware standpoint identical to the RS485 extension, because Modbus is just an RS485 bus anyway. However it does encode and decode the Modbus protocol.

Send write command to Modbus

The Modbus Extension only supports a limited number of write functions. Because of that, I have simply listed them all, which is much easier to read than trying to understand the Loxone documentation.

The extension listens to 0x5D..0x62, which are all used to control actuators (= setting registers on the Modbus). The parameters are as such: B0=1, B1/B2 the 16-bit register number. B3/B4 or B3-B6: 2 or 4 bytes of data. The commands are converted into the following Modbus functions. Warning: the values are in big-endian format!

Digital Actuator:

  • 0x5D: Write single coil (5), 2 bytes (ON:0xFF,0x00 OFF:0x00,0x00)
  • 0x5E: Preset single register (6), 2 bytes (ON:0x0001 OFF:0x0000)
  • 0x63: Force multiple coils (15), 2 bytes (ON:0xFF,0x00 OFF:0x00,0x00)
  • 0x5F: Preset multiple registers (16), 2 bytes (ON:0x0001 OFF:0x0000)

Analog Actuator with 16-bit unsigned integers (B3/B4:aabb):

  • 0x5D: Write single coil (5), 2 bytes
  • 0x5E: Preset single register (6), 2 bytes
  • 0x63: Force multiple coils (15), 2 bytes
  • 0x5F: Preset multiple registers (16), 2 bytes

Analog Actuator with 32-bit values (B3-B6:aabbccdd):

  • 0x5D: Write single coil (5), 2 bytes
  • 0x61: Preset single register (6), 4 bytes
  • 0x63: Force multiple coils (15), 2 bytes
  • 0x62: Preset multiple registers (16), 4 bytes

32-bit floating point numbers are transmitted as IEEE–754 32-bit values, again: in big-endian!

Command Modbus write function Modbus telegram
0x5D Single Coil B0 0x05 B1 B2 B3 B4 CRC16-Modbus
0x5E Single Register B0 0x06 B1 B2 B3 B4 CRC16-Modbus
0x5F Multiple Registers B0 0x10 B1 B2 0x00 0x01 B3 B4 CRC16-Modbus
0x60 Multiple Registers (2 regs) B0 0x10 B1 B2 0x00 0x02 B3 B4 B5 B6 CRC16-Modbus
0x61 Single Register (4-bytes) B0 0x06 B1 B2 B3 B4 B5 B6 CRC16-Modbus
0x62 Multiple Registers (4-bytes) B0 0x10 B1 B2 0x00 0x01 B3 B4 B5 B6 CRC16-Modbus

B0 is the address of the device B1/B2 is the start register number. Loxone uses LSB for 16-bit, but Modbus MSB. B3-B6 are data values

Reading registers

The Modbus extension calls the Modbus read function automatically and sends the values back to the Miniserver. It has to be configured for that. This is done by uploading the configuration via a fragmented package of type 0x06 (config). The configuration is 0x810 bytes large and always version 1.

Offset Type Description
0 32-bit 0xFEEDFEED = magic to detect that the package is valid
4 16-bit Version of the settings, always 1
6 8-bit 0:automatic timing (based on the baudrate), !=0:manual timing flag (timing pause and timing timeout are used)
7 8-bit 0x00, unused filler
8 32-bit baudrate (2400,4800,9600 or 19200 are typical)
0x0C 8-bit wordlength (5,6,7,8, Modbus requires 8)
0x0D 8-bit parity (0=no parity, not in the Modbus specification, but very common)
0x0E 8-bit one/two stop-bits (0=one stop-bit)
0x0F 8-bit protocol == 3 (Modbus?)
0x10 32-bit timing pause, default: 10ms between packages
0x14 32-bit timing timeout, default: 1000ms for a response
0x18 32-bit number of entries in the following table
0x1C 8 byte packages entries for read function requests
0x80C 32-bit 0x000000, zero filler

Description of a single 8-byte entry:

Offset Description
0 1…255: Address of the Modbus device (0 would be broadcast)
1 Modbus function code
2 16-bit register number
4 32-bit polling cycle and flags

The 32-bit value is a bit complex:

Bit(s) Description
0…11 polling cycle
12 0:100ms, 1:1000ms; factor for the polling cycle to have the delay in ms
13 1:combine 2 registers for a 32-bit value
14 register order (0:low/high, 1:high/low)
15 byte order (0:MSB, 1:LSB)

The Modbus extension enforces a minimal 5s polling interval. A custom Modbus extension may not enforce it.

With the configuration uploaded and the extension not muted, the Modbus extension will send all polling requests based on the timing, but only one per 2ms. The send request is created from the entry table as follows:

For read coils (1) and read discrete inputs (2):

`address` `function code` `MSB register number` `LSB register number` 0x00 0x01 CRC16-Modbus

For read holding registers (3) and read input register (4):

`address` `function code` `MSB register number` `LSB register number` 0x00 0x01/0x02 CRC16-Modbus

The 0x01/0x02 is depended if bit 13 (combine 2 registers) is set or not.

For any other function code:

`address` `function code` `MSB register number` `LSB register number` CRC16-Modbus

The reply is parsed (based on the function code and the bits in the polling cycle flags) and send back to the Miniserver. If an error occurs, an error command is reported back:

Command B0 B1/B2 B2/B3 B4/B6 Description
0x1C Modbus address 0 Value Low Value High Confirmation from a write function (Write Single Coil, Write Single Register, Write Multiple Coils, Write Multiple Registers) with the new value
0x1C Modbus address 1 Modbus register following 2 bytes after Modbus register No response from the Modbus device
0x1C Modbus address 2 Modbus register 0x0000 Package had a CRC error
0x1C Modbus address 3 Modbus register 16-bit value Invalid response, e.g. from a different Modbus device or just garbage with a correct CRC
0x1C Modbus address 4 Modbus register 0x0000 Invalid package length
0x1C Modbus address 5 Modbus register 16-bit value Unexpected error, e.g. an unknown function code
0x1C Modbus address 6 ? ? TX queue overrun (not sure if this one can happen)
0x5C Modbus address 0 Value Low Value High The non-error reply contains the requested 32-bit value

The value is send as a 32-bit value, it is extracted from the Modbus package in this way. pkt is the received Modbus package as specified in the Modbus documentation.

  • read coils (1), read discrete inputs (2) simply return pkt[3]
  • read exception status (7) returns pkt[2]
  • read holding registers (3), read input register (4) checks if combine two registers (bit 13) is set. If so it takes a 32-bit value from pkt[3-6]. If the register order (bit 14) is set, then the upper/lower 16-bit are swapped. Then the byte order (bit 15) is applied. If a single 16-bit register is read (bit 13 is cleared), then a 16-bit from pkt[3-4] is read and only the byte order (bit 15) need to be applied.