function ds = case17()
% Z. Ghofrani-Jahromi, Z. Mahmoodzadeh and M. Ehsan, "Distribution Loss
% Allocation for Radial Systems Including DGs," in IEEE Transactions on Power
% Delivery, vol. 29, no. 1, pp. 72-80, Feb. 2014.
% doi: 10.1109/TPWRD.2013.2277717
ds.Uslack = 1;
ds.Ubase = 20; % Base voltage, line-to-line (kV)
ds.Sbase = 1; % Base power (MVA)
ds.branch = [
% From To R(pu) X(pu) B(pu) P(kW) Q(kvar) Qc(kvar)
1 2 0.0025 0.0026 0.03 0 0 0
2 5 0.0007 0.0007 0.02 140 80 0
2 3 0.0008 0.0008 0.02 89 50 0
3 4 0.0007 0.0007 0 111 63 0
5 9 0.0021 0.0022 0.02 89 50 0
5 6 0.002 0.0021 0.02 0 0 0
6 10 0.0001 0.0001 0 0 0 0
6 7 0.0009 0.0009 0.01 141 80 0
7 8 0.0017 0.0017 0.01 338 192 0
10 11 0.0006 0.0006 0 152 86 0
10 12 0.0018 0.0018 0 266 151 0
12 13 0.0003 0.0003 0 10 5 0
12 14 0.0011 0.0011 0 0 0 0
14 15 0.0011 0.0011 0 205 116 0
14 17 0.0007 0.0007 0 241 137 0
15 16 0.0001 0.0001 0 72 41 0
];
Zbase = ds.Ubase^2/ds.Sbase;
ds.branch(:,3:4) = ds.branch(:,3:4) * Zbase;
ds.branch(:,5) = ds.branch(:,5) / Zbase * 1e6;
ds.gen = [
% Bus P(kW) Q(kvar) U(pu) Type (1-PQ, 2-PU)
15 300 145.29 1.00 1
16 200 96.86 1.00 1
17 260 125.92 1.00 1
];