Data Center Power System - Availability Analysis of Redundancy Alternatives

alt text

Date: 2/4/2025

Background:

Data centers are expanding in number and in size at a rapid pace. Data centers require a significant amount of electrical power at high availability. Availability metrics for data centers are defined by Uptime Institute according to a Tier Level. Uptime Institute's categorization of Tier level includes an availability metric as follows:

  • Tier 1: Reliability >= 99.671
  • Tier 2: Reliability >= 99.741
  • Tier 3: Reliability >= 99.982
  • Tier 4: Reliability >= 99.995

This metric refers to the data center availability which as a consequence dictates the power system availability being equal to or even greater than this value. For simplicity, I have assumed that the power system must equal these availabiltiy levels to be classified according to the respective tier.

Reliability is defined as the measure of unplanned (forced) outage time divided by period hours. Reliability is therefore a probabablistic measure.

Availability accounts for unplanned and planned or scheduled outages.

Program Objective:

  • The objective of the program is to calculate the availability of a power system, given a demand load, individual unit reliability and annual scheduled outage hours per unit.
  • Following user input, the program calculates the system availability for different unit size and unit redundancy cases (n+0, n+1, n+2, n+3, n+4, n+5).
  • For each case, the program calculates the system reliability under two conditions:
    • Condition 1: no units in scheduled outage
    • Condition 2: 1 unit in scheduled outage
  • An average annual system reliability is calculated based on a period weighting average of the two conditions.
  • The program is built as a web application using Flask.

Program Structure:

The program consists of the following features and modules:

1. User Input:  
-  Solicits user input via. the terminal prompt for 
    - demand_load 
    - unit_reliability 
    - annual scheduled outage duration per unit
- Returns a dataframe with all cases and case definitions
    - Demand load as supplied by the user 
    - 2-5 units required and sized to meet the demand load without redundancy
    - 0-5 redundant units of the same size
    - Individual unit reliability as supplied by the user
    - Individual unit scheduled outage hours as supplied by the user
    - Calculated system capacity based on unit sizes and total units (reqd + redundant) 

2. Plots: 
-  Results plots are created using plotly and converted to html for rendering on the web app:
    - Availability vs. System Capacity Scatter Plotting.
    - BoxPlot of System Capacity by Tier Level.
    - Subplots of System Capacity vs. Number of Units shown for each Tier level. (example below)

alt text

Authors

About Me

I'm Bill—a power industry professional with 20+ years of experience in power generation. My background as a mechanical engineer led to me a role as project manager where I led the development and execution of power generation projects. These days, I'm practicing, python, data science, visualization, and machine learning skills with the intention of using them as a tool to uncover insights and improve decision making in power project development, design, procurement, construction and operations.