SNMP Agent Features

A simple SNMP agent is implemented with a ported version of "Agentuino" Library by Eric C. Gionet lavco_eg@hotmail.com which was also extended by Petr Domorazek. The portation was required so that the library is capable of running on WiFiNINA based devices (tested with Arduino Nano 33 IoT) instead of using an EthernetShield.

The ported version is available on Github https://github.com/ANSnullANS/Agentuino.

Configuration

RoomGuard is listening on port 161/upd (default SNMP port).

The values for Name, Contact and Location (RFC1213) are limited to 32 characters by default to safe memory. Increase their array-size in "snmp_config.h" if needed.

Without SD-Card

In "config.h":

  • make sure that #define SNMP_ENABLED true is NOT commented out!
  • make sure that #define SNMP_SDCONFIG true is commented out!

In "snmp_config.h":

  • Update value of char locContact[32] PROGMEM to your local Contact for this RoomGuard Device.
  • Update value of char locName[32] PROGMEM to the Name of this RoomGuard Device (use whatevery feels right ;) ).
  • Update value of char locLocation[32] PROGMEM to the physical location of this RoomGuard Device.

Load config from SD-Card

This requires that all settings are loaded from SD-Card (rg.cfg)!

In "config.h":

  • make sure that #define SNMP_ENABLED true is NOT commented out!
  • make sure that #define SNMP_SDCONFIG true is NOT commented out!

On SD-Card:

  • create new file named "snmp.cfg"
  • Insert values into "snmp.cfg": -- Name of this RoomGuard Device (e.g. roomguard01) -- Location (e.g. Server-Room) -- Contact (e.g. Paco Lechner)

Implemented Parameters

All parameters are implemented for SNMPGET only!

MIB

If you're using any SNMP-Collector which is capable of working with MIB files, copy "ROOMGUARD-MIB.txt" to it's MIB-Storage and/or load the MIB manually.

List of OIDs

If you're implementing some monitoring manually, use the following OIDs in your SNMPGET requests.

RFC1213-MIB

Parameter OID Datatype Description
sysDescr 1.3.6.1.2.1.1.1 DisplayString Name of the Device
sysUpTime 1.3.6.1.2.1.1.3 TimeTicks Uptime of the Device
sysContact 1.3.6.1.2.1.1.4 DisplayString Contact for this Device
sysName 1.3.6.1.2.1.1.5 DisplayString Name of the Device
sysLocation 1.3.6.1.2.1.1.6 DisplayString Location of the Device

ROOMGUARD-MIB

Parameter OID Datatype Description
WiFi SSID 1.3.6.1.4.1.1600.1.1.1 DisplayString Configured SSID
WiFi Status 1.3.6.1.4.1.1600.1.1.2 DisplayString Status-String for WiFi Connection
WiFi Signal 1.3.6.1.4.1.1600.1.1.3 Integer32 Signal Strength in dBm
Sensor0 Temperature 1.3.6.1.4.1.1600.1.2.1.1 Integer Temperature from Sensor0 as integer (divide by 10 to get real value)
Sensor0 Humidity 1.3.6.1.4.1.1600.1.2.1.2 Integer Humidity from Sensor0 as integer (divide by 10 to get real value)
Arduino RAM Total 1.3.6.1.4.1.1600.1.100.1 Integer Total RAM of Arduino MCU
Arduino RAM Free 1.3.6.1.4.1.1600.1.100.2 Integer Free RAM of Arduino MCU