Merge pull request #1477 from shambergoldstein/air-system-additions
Browse files Browse the repository at this point in the history
Air System Additions
  • Loading branch information
ccquigley authored Dec 13, 2024
2 parents b3d2bbc + 5d4b744 commit 7b2b04d
Show file tree
Hide file tree
Showing 10 changed files with 182 additions and 19 deletions.
29 changes: 28 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -807,7 +807,9 @@ SS:
- communication_status
- efficiency_percentage_sensor
- load_percentage_sensor
- optimal_stop_command
- request_run_command
- schedule_run_command

DSPC:
guid: "3f288511-32ca-47ae-a4e0-391620026420"
Expand Down Expand Up @@ -1055,7 +1057,6 @@ LHC:
implements:
- CONTROL


SFSS:
guid: "1e8dd2f7-192a-430b-af2c-db6065664deb"
description: "Basic combination of supply fan run command and status (start/stop)."
Expand All @@ -1071,10 +1072,29 @@ SFSS:
- supply_fan_run_time_accumulator
- failed_supply_fan_alarm
- supply_fan_lost_power_alarm
- schedule_run_command
- optimal_stop_command
uses:
- supply_fan_run_command
- supply_fan_run_status

SFFM:
guid: "81a4d943-661e-4d61-aae7-ba009a481f78"
description: "Supply air flowrate monitoring for individual supply fans within an array."
is_abstract: true
implements:
- OPERATIONAL
opt_uses:
- supply_air_flowrate_sensor_1
- supply_air_flowrate_sensor_2
- supply_air_flowrate_sensor_3
- supply_air_flowrate_sensor_4
- supply_air_flowrate_sensor_5
- supply_air_flowrate_sensor_6
- supply_air_flowrate_sensor_7
- supply_air_flowrate_sensor_8
uses:
- total_supply_air_flowrate_sensor

RHM:
guid: "9b13e30c-52b7-45d1-9798-f7c754e959e9"
Expand Down Expand Up @@ -1887,6 +1907,7 @@ REFC:
opt_uses:
- failed_zone_air_refrigerant_concentration_alarm
- high_zone_air_refrigerant_concentration_alarm
- refrigerant_leak_detection_status
uses:
- zone_air_refrigerant_concentration_sensor
- zone_air_refrigerant_concentration_setpoint
Expand Down Expand Up @@ -2277,6 +2298,7 @@ CHWSC:
- low_supply_air_temperature_alarm
- water_leak_alarm
- frost_alarm
- cooldown_run_command
uses:
- chilled_water_valve_percentage_command
- supply_air_temperature_sensor
Expand Down Expand Up @@ -3285,6 +3307,8 @@ HWSC:
- failed_supply_air_temperature_alarm
- high_supply_air_temperature_alarm
- low_supply_air_temperature_alarm
- warmup_request_count
- warmup_run_command
uses:
- heating_water_valve_percentage_command
- supply_air_temperature_sensor
Expand Down Expand Up @@ -4021,6 +4045,8 @@ VOADM:
- low_mixed_air_temperature_alarm
- failed_outside_air_damper_alarm
- failed_outside_air_temperature_alarm
- outside_air_flowrate_sensor
- ventilation_request_count
uses:
- outside_air_damper_percentage_command
- outside_air_temperature_sensor
Expand Down Expand Up @@ -8561,6 +8587,7 @@ HP6SWC:
- heating_thermal_power_capacity
- high_supply_water_temperature_alarm
- low_supply_water_temperature_alarm
- return_water_temperature_sensor
uses:
- compressor_run_command_1
- compressor_run_command_2
Expand Down
69 changes: 68 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/AHU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -2280,6 +2280,25 @@ AHU_CHWSC_ECON_EFSS_EFVSC_FDPM_RFC_SFSS_SFVSC_SSPC:
- SFVSC
- SSPC

AHU_CHWSC_ECONM_EFSS_EFVSC_FDPM_RFC_SFSS_SFVSC_SSPC_RFSS_RFVSC_DSARC:
guid: "691e5aa7-4ba6-4aa1-a023-ff875c8fd35a"
description: "Multi-zone AHU with variable speed supply, exhaust, and return fans."
is_canonical: true
implements:
- AHU
- CHWSC
- ECONM
- EFSS
- EFVSC
- FDPM
- RFC
- SFSS
- SFVSC
- SSPC
- RFSS
- RFVSC
- DSARC

AHU_BSPC_DX4SC_ECONM_EFSS_EFVSC_OAFMC_SFSS_SFVSC_SSPC:
guid: "4a9f69bb-5f8b-41aa-aa92-3e4f85dd5bf8"
description: "Multi-zone AHU."
Expand Down Expand Up @@ -2638,6 +2657,20 @@ AHU_CHWSC_ECONM_FDPM_HWSC_SFSS_STC:
- SFSS
- STC

AHU_CHWSC_ECONM_FDPM_HWSC_SFSS_STC_DSARC:
guid: "b636cac2-6985-4a8e-b962-448c686c64b7"
description: "Multi-zone AHU."
is_canonical: true
implements:
- AHU
- CHWSC
- ECONM
- FDPM
- HWSC
- SFSS
- STC
- DSARC

AHU_CHWSC_ECONM_FDPM_HWSC_SFSS_SFVSC_SSPC_SARC:
guid: "2f8c18be-23c4-4fdc-a7af-4a90e9a93e9d"
description: "Multi-zone AHU."
Expand All @@ -2653,6 +2686,20 @@ AHU_CHWSC_ECONM_FDPM_HWSC_SFSS_SFVSC_SSPC_SARC:
- SSPC
- SARC

AHU_CHWSC_ECONM_FDPM_HWSC_SFSS_SFVSC_SSPC_DSARC:
guid: "f72e1b2b-c110-4e6a-90b8-6a046296c8ed"
description: "Multi-zone AHU."
is_canonical: true
implements:
- AHU
- CHWSC
- ECONM
- FDPM
- HWSC
- SFSS
- SFVSC
- SSPC
- DSARC

AHU_EDBPC_DX4SC_ECONM_EFSS_EFVSC_SFSS_SFVSC_SARC_SSPC:
guid: "9d123538-8cb1-4ad7-b712-4cce9693caaf"
Expand Down Expand Up @@ -4379,6 +4426,26 @@ AHU_CHWSC_ECON_FDPM_HWSC_SFSS_SFVSC_SSPC_SDHC_RTM:
opt_uses:
- smoke_alarm

AHU_CHWSC_ECON_VOADM_FDPM_HWSC_SFSS_SFVSC_SFFM_SSPC_SDHC_RTM:
guid: "68f0f604-9e65-44b2-b8e9-ea93bf118665"
description: "Multi-zone AHU with multi-supply fan flowrate monitoring, dehumidifier and return temperature monitoring"
is_canonical: true
implements:
- AHU
- CHWSC
- ECON
- VOADM
- FDPM
- HWSC
- SFSS
- SFVSC
- SFFM
- SSPC
- SDHC
- RTM
opt_uses:
- smoke_alarm

AHU_SFSS4X_SFVSC4X_RFSS3X_RFVSC3X_CHWSC_HWSC_ECON_EDBPC_SARC_SSPC_RD_OAFMC_EFM:
guid: "187ad041-6b1e-4ee5-aabb-69dc8c287bdd"
description: "Cooling and heating AHU with 4 supply and 3 return fans, supply air reset control, building and supply static pressure control, return damper flow control and exhaust flow monitoring."
Expand Down Expand Up @@ -5602,4 +5669,4 @@ AHU_BSPC_DX4SC_ECON_EFSS_EFVSC_SFSS_SFVSC_SSPC_RHHC_NONCANONICAL_1:
uses:
- heating_water_valve_percentage_command
- min_zone_air_relative_humidity_sensor
- min_zone_air_relative_humidity_setpoint
- min_zone_air_relative_humidity_setpoint
3 changes: 1 addition & 2 deletions ontology/yaml/resources/HVAC/entity_types/CDWS.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -186,14 +186,13 @@ CDWS_SWTC_BYPVPM_WFRM_MWFRM_BWFRM:
- MWFRM
- BWFRM

CDWS_SS_SRC_SWTC_BYPVPM_WFRM_MWFRM_BWFRM:
CDWS_SS_SWTC_BYPVPM_WFRM_MWFRM_BWFRM:
guid: "27d51584-886f-4142-8e8a-17af27aa9fec"
description: "Condensing water system (temp control) with bypass control, flow monitoring and basin water system"
is_canonical: true
implements:
- CDWS
- SS
- SRC
- SWTC
- BYPVPM
- WFRM
Expand Down
10 changes: 4 additions & 6 deletions ontology/yaml/resources/HVAC/entity_types/CH.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -679,14 +679,13 @@ CH_SS_VSC_CHDXSC_SCHWTC_CWSISOVPM_CHWSWISOVM_CHWDPM_CWDT_REFPM_REFSM:
- REFPM
- REFSM

CH_SS_SRC_VSC_CHDXSC_SCHWTC_CWSISOVPM_CHWSWISOVM_CHWDPC_CWDPC_CWDT_REFPM_REFSM:
CH_SS_VSC_CHDXSC_SCHWTC_CWSISOVPM_CHWSWISOVM_CHWDPC_CWDPC_CWDT_REFPM_REFSM:
guid: "8c69f993-c5eb-46f1-a1f1-964cc8b4cbdf"
description: "Water cooled chiller with schedule run control, condensing and chilled supply water isolation valves, condensing water temperature differential monitoring, chilled and condensing water differential pressure control and single circuit refrigerant pressure and temperature monitoring."
description: "Water cooled chiller with run control, condensing and chilled supply water isolation valves, condensing water temperature differential monitoring, chilled and condensing water differential pressure control and single circuit refrigerant pressure and temperature monitoring."
is_canonical: true
implements:
- CH
- SS
- SRC
- VSC
- CHDXSC
- SCHWTC
Expand Down Expand Up @@ -714,14 +713,13 @@ CH_SS_DX3SCHWC_CWSISOVM_CWRISOVM_CHWSWISOVM_CHWDPM_CWDT_CHWDT_RCKTM:
- CHWDT
- RCKTM

CH_SS_SRC_DX3SCHWC_CWSISOVM_CWRISOVM_CHWSWISOVM_CHWDPC_CWDPC_CHWHRDPC_CWHRDPC_CWDT_CHWDT_RCKTM:
CH_SS_DX3SCHWC_CWSISOVM_CWRISOVM_CHWSWISOVM_CHWDPC_CWDPC_CHWHRDPC_CWHRDPC_CWDT_CHWDT_RCKTM:
guid: "8a648fa7-d065-4ff4-b524-626b4a23c238"
description: "Water cooled chiller with schedule run control, three compressors, refrigeration circuit monitoring, condensing supply and return water isolation valve, chilled supply water islation valve, chilled and condensing water differential pressure control, heat recovery, and condensing water temperature differential monitoring."
description: "Water cooled chiller with run control, three compressors, refrigeration circuit monitoring, condensing supply and return water isolation valve, chilled supply water islation valve, chilled and condensing water differential pressure control, heat recovery, and condensing water temperature differential monitoring."
is_canonical: true
implements:
- CH
- SS
- SRC
- DX3SCHWC
- CWSISOVM
- CWRISOVM
Expand Down
11 changes: 5 additions & 6 deletions ontology/yaml/resources/HVAC/entity_types/CHWS.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -496,26 +496,25 @@ CHWS_SWTC_WDPM_CLPM_WFRM:
- CLPM
- WFRM

CHWS_SRC_SWTC_WDPC_CLPM_WFRM:
CHWS_SS_SWTC_WDPC_CLPM_WFRM:
guid: "8448f024-bfc7-46e9-9d91-19949aef2477"
description: "Chilled water system with schedule run command, cooling thermal power monitoring, supply water temperature control, differential pressure control and flowrate monitoring."
description: "Chilled water system with run command, cooling thermal power monitoring, supply water temperature control, differential pressure control and flowrate monitoring."
is_canonical: true
implements:
- CHWS
- SRC
- SS
- SWTC
- WDPC
- CLPM
- WFRM

CHWS_SS_SRC_WDPC_SWISOVPM_BYPVPM_WSEBYPVPM_PWDT_PRSWFRC_SESWTC_SEWFRM_CLPM:
CHWS_SS_WDPC_SWISOVPM_BYPVPM_WSEBYPVPM_PWDT_PRSWFRC_SESWTC_SEWFRM_CLPM:
guid: "49477bff-e5f7-42bc-b498-8965f4ed3e41"
description: "Chilled water system with schedule run command, cooling thermal power monitoring, primary and secondary water control, and water side economizing."
description: "Chilled water system with run command, cooling thermal power monitoring, primary and secondary water control, and water side economizing."
is_canonical: true
implements:
- CHWS
- SS
- SRC
- WDPC
- SWISOVPM
- BYPVPM
Expand Down
23 changes: 22 additions & 1 deletion ontology/yaml/resources/HVAC/entity_types/FAN.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -283,6 +283,17 @@ FAN_SS_VSC_EPC:
- VSC
- EPC

FAN_SS_VSC_EPC_EDPM:
guid: "450f5cba-4c92-4aaf-b068-628a0cd7400d"
description: "Fan with run control, exhaust static pressure control and exhaust damper monitoring."
is_canonical: true
implements:
- FAN
- SS
- VSC
- EPC
- EDPM

FAN_SS_DSP_VSC:
guid: "660d42d5-15b3-4cb4-9af1-506f31b0aa0e"
description: "Fan with dual setpoint control and variable speed."
Expand Down Expand Up @@ -692,6 +703,16 @@ FAN_SS_VSC_REFC:
- VSC
- REFC

FAN_SS_HLC_REFC:
guid: "b0ad4fce-417b-420c-afad-49dcd2268521"
description: "Fan with start/stop status, high/low speed control and refrigerant concentration control."
is_canonical: true
implements:
- FAN
- SS
- HLC
- REFC

FAN_SS_VSC_ZSPM_DWI:
guid: "a1148f7d-4aa0-4560-b2cb-53b8eb949278"
description: "Dishwasher-interlocked fan with start/stop status, open-loop speed control, and zone static pressure monitoring."
Expand Down Expand Up @@ -1002,4 +1023,4 @@ FAN_SS_NONCANONICAL_8:
uses:
- discharge_air_isolation_damper_closed_status
- discharge_air_isolation_damper_command
- discharge_air_isolation_damper_open_status
- discharge_air_isolation_damper_open_status
14 changes: 12 additions & 2 deletions ontology/yaml/resources/HVAC/entity_types/HWS.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -105,6 +105,16 @@ HWS_RWTC_MXVPM:
- RWTC
- MXVPM

HWS_SS_RWTC_MXVPM:
guid: "a78c552b-667d-43eb-9418-afe7486a7ee2"
description: "Heating water system with run control and mixed return temp control."
is_canonical: true
implements:
- HWS
- SS
- RWTC
- MXVPM

HWS_SWTC_BYPVPM:
guid: "8d8652a9-6814-413e-9aa1-8772a831d6a3"
description: "Heating water system with supply temp control and bypass."
Expand Down Expand Up @@ -405,13 +415,13 @@ HWS_PWDT_SESWTC_SEWDPC_SERWFRM_SEWTM:
- SERWFRM
- SEWTM

HWS_SRC_SWTC_WDPC_WFRM_HWTTC_HLPM:
HWS_SS_SWTC_WDPC_WFRM_HWTTC_HLPM:
guid: "b203359c-877b-4c46-903e-57c4c5b4d634"
description: "Heating water system with schedule run command, heating thermal power monitoring, supply water temperature control, differential pressure control, flowrate monitoring, and hot water tank temperature control."
is_canonical: true
implements:
- HWS
- SRC
- SS
- SWTC
- WDPC
- WFRM
Expand Down
20 changes: 20 additions & 0 deletions ontology/yaml/resources/HVAC/entity_types/MAU.yaml
Original file line number Diff line number Diff line change
Expand Up @@ -786,6 +786,26 @@ MAU_SFSS2X_SFVSC2X_CHWSC_HWSC_SSPC_VOADM_FDPM_ZSPM_OAFM:
opt_uses:
- smoke_alarm

MAU_SS_SFSS2X_SFVSC2X_SFFM_CHWSC_HWSC_SSPC_VOADM_FDPM_ZSPM_OAFM:
guid: "9b0256de-6e1d-4fc0-abc2-c751c4e209c8"
description: "Multi-zone chilled water and heating water MAU with run control, supply air static pressure control, variable outside air damper and outside airflow monitoring, filter differential pressure monitoring, zone static pressure monitoring."
is_canonical: true
implements:
- MAU
- SS
- SFSS2X
- SFVSC2X
- SFFM
- CHWSC
- HWSC
- SSPC
- VOADM
- FDPM
- ZSPM
- OAFM
opt_uses:
- smoke_alarm

MAU_DFSS_DFVSC_DSP_CHWDC_HWDC_OADM_ZSPM:
guid: "9ba6dc9b-1b5b-4f05-8be2-2ff4b0bb7390"
description: "Single zone heating and cooling make-up air unit with zone static pressure control and outside air temperature monitoring."
Expand Down